Tekniset tiedot
Product properties
Product type Hybrid motor starters
Product family CONTACTRON
Operating mode 100% operating factor
Electrical properties
Number of phases 3
Motor starter type Reversing starter
Maximum power dissipation for nominal condition 4.4 W
Switching frequency ≤ 2 Hz (Load-dependent)
Maximum power dissipation 5.5 W
Minimum power dissipation 0.88 W
Coordination type 2
Supply
Rated control circuit supply voltage US 24 V DC
Control supply voltage range 19.2 V DC … 30 V DC
Rated control supply current IS 40 mA
Protective circuit Surge protection
Reverse polarity protection; Parallel polarity protection diode
Insulation characteristics
Rated insulation voltage 500 V
Rated surge voltage 6 kV
Overvoltage category III
Degree of pollution 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) at operating voltage 300 V AC … 500 V AC
Safe isolation (EN 50178) at operating voltage 300 … 500 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuit Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Input data
Control
Input name Control input right/left
Rated actuating voltage UC 24 V DC
Triggering voltage range 19.2 V DC … 30 V DC
Rated actuating current IC 5 mA
Switching threshold 9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level < 5 V DC (For EMERGENCY STOP)
Typical turn-off time < 30 ms
Protective circuit Reverse polarity protection
Output data
AC output
Rated operating voltage Ue 500 V AC
Operating voltage range 42 V AC … 550 V AC
Mains frequency 50/60 Hz
Load current range 180 mA … 2.4 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2 Class 10A
Cooling time 20 min. (for auto reset)
Leakage current 0 mA
Protective circuit Surge protection; Varistor
Short-circuit protection; Fuse
Acknowledge output
Note Confirmation: floating change-over contact, signal contact
Contact switching type 1 changeover contact
Switching capacity in accordance with IEC 60947-5-1 3 A (230 V, AC15)
2 A (24 V, DC13)
Connection data
Control circuits
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² … 2.5 mm²
Conductor cross section flexible 0.2 mm² … 2.5 mm²
Conductor cross section AWG 24 … 14
Tightening torque 0.5 Nm … 0.6 Nm
5 lbf-in. … 7 lbf-in.
Load circuit
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² … 2.5 mm²
Conductor cross section flexible 0.2 mm² … 2.5 mm²
Conductor cross section AWG 24 … 14
Tightening torque 0.5 Nm … 0.6 Nm
5 lbf-in. … 7 lbf-in.
Signaling
Status display Yellow LED
Operating voltage display Green LED
Error indication Red LED
Dimensions
Width 22.5 mm
Height 160 mm
Depth 114.5 mm
Material specifications
Flammability rating according to UL 94 V0 (Housing)
Environmental and real-life conditions
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C … 80 °C
Altitude ≤ 2000 m
Approvals
ATEX
Identification II (2) G [Ex e] [Ex d] [Ex px]
II (2) D [Ex t] [Ex p]
Certificate PTB 12 ATEX 3004
UL approval
Certificate NLDX.E228652
Safety Integrity Level (SIL, IEC 61508)
Identification ≤ 3
Note Safe shutdown
Safety Integrity Level (SIL, IEC 61508)
Identification 2
Note Motor protection
Performance Level (ISO 13849)
Identification e
Note Safe shutdown
Category (ISO 13849)
Identification ≤ 3
Note Safe shutdown
CCC
Identification GB/T 14048.6-2016
Certificate 2020970304000811
UL data
SCCR 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
FLA 2.4 A (500 V AC)
Group installation 20 A (class RK5, SCCR 5kA, #24 – 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 – 14 AWG max, solid and stranded)
Category code NLDX / NRNT
Standards/regulations
Standards/regulations IEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849
Mounting
Mounting type Bus bar mounting
DIN rail mounting
Assembly instructions alignable, for spacing see derating
Mounting position vertical (horizontal DIN rail, motor output below)
Muut tiedot
Tuotenumero 2902744
Pakkausyksikkö 1 Kappaletta
Tuoteavain CK7452
Tuotekoodi CK7452
GTIN 4046356674539
Paino kappaletta kohti (sis. pakkauksen) 426,533 g
Paino kappaletta kohti (ilman pakkausta) 350 g
Tullitariffinumero 85371098
Alkuperämaa DE