Dimensions
Product Net Width:45 mm
Product Net Height:90 mm
Product Net Depth / Length:86.75 mm
Product Net Weight:0.265 kg
Technical
Rated Service Short-Circuit Breaking Capacity (Ics):(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 100 kA
(500 V AC) 100 kA
(690 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):(230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 100 kA
(500 V AC) 100 kA
(690 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):31.3 A
Setting Range:None
Rated Operational Power AC-3 (Pe):(400 V) Three Phase 0.75 kW
Rated Operational Power AC-3e (Pe):(400 V) Three Phase 0.75 kW
Rated Operational Voltage:Main Circuit 690 V AC
Rated Operational Current (Ie):2.5 A
Rated Operational Current AC-3 (Ie):2.5 A
Rated Operational Current AC-3e (Ie):2.5 A
Rated Frequency (f):Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw):0 … 400 Hz
Rated Impulse Withstand Voltage (Uimp):Main Circuit 6 kV
Rated Insulation Voltage (Ui):690 V
Power Loss:at Rated Operating Conditions per Pole 1.7 W
Number of Poles:3
Conventional Free-air Thermal Current (Ith):Main Circuit 2.5 A
Degree of Protection:Housing IP20
Main Circuit Terminals IP10
Pollution Degree:3
Electrical Durability:50000 cycle
Mechanical Durability:100000 cycle
Terminal Type:Screw Terminals
Connecting Capacity Main Circuit:Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 … 2.5 mm²
Flexible 1/2x 0.75 … 2.5 mm²
Rigid 1/2x 1 … 4 mm²
Tightening Torque:Main Circuit 0.8 … 1.2 N·m
Wire Stripping Length:Main Circuit 9 mm
Recommended Screw Driver:Pozidriv 2
Mounting Position:1 … 6
Mounting on DIN Rail:TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:Electrical Conductive Board, Horizontal – Up to 400 V 0 mm
Electrical Conductive Board, Horizontal – Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Actuator Type:Rotary Handle
Contact Position Indication:ON / OFF / TRIP
Standards:IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Remarks:For overload protection of the motors, an appropriate thermal or electronic overload relays must be used