Dimensions
Product Net Width:70 mm
Product Net Height:100 mm
Product Net Depth / Length:74 mm
Product Net Weight:0.36 kg
Technical
Rated Operational Current AC-21A (Ie):(500 V) 63 A
(380 … 415 V) 63 A
(690 V) 63 A
Rated Operational Current AC-22A (Ie):(380 … 415 V) 63 A
(500 V) 63 A
(690 V) 63 A
Rated Operational Current AC-23A (Ie):(380 … 415 V) 63 A
(500 V) 63 A
(690 V) 40 A
Rated Operational Power AC-23A (Pe):(380 … 415 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
Rated Impulse Withstand Voltage (Uimp):8 kV
Rated Insulation Voltage (Ui):acc. to IEC/EN 60664-1 750 V
Rated Operational Voltage:Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm):(690 V) 3.6 kA
Rated Short-time Withstand Current Low Voltage (Icw):for 1 s 2.5 kA
Rated Conditional Short-Circuit Current (Inc):(125 A fuse, 415 V) 50 kA
(125 A fuse, 690 V) 10 kA
(63 A fuse, 690 V) 50 kA
Power Loss:at Rated Operating Conditions per Pole 1.6 W
Pollution Degree:3
Handle Type:Knob
Handle and shaft not included
Switches Operating Mechanism:Mechanism on Top of the Switch
Distance Between Phases:Standard
Position of Line Terminals:Top In – Bottom Out
Bottom In – Top Out
Operating Mode:Front operated
Standards:IEC 60947-3 / UL 98 / CSA C22.2 NO.4
Special Functions:No
Mounting Type:Base mounting
Number of Poles:3
Cable Cross-Section:Cu 2.5 … 25 mm²
Degree of Protection:Front IP20
Terminal Type:Screw Terminals
Tightening Torque:acc. IEC 60947-1 6.2 N·m
Mechanical Durability:20000
Lock Type:No